根据湖北地区2008年2月和2009年1月500 k V高压输电线实时观测资料,结合MICAPS常规气象资料和NCEP再分析资料,研究了湖北张恩高压输电线上电线积冰形成的天气形势和气象条件。结果表明:两次积冰过程中500 h Pa深厚的低压槽和850 h Pa低涡配合切变线靠近湖北促使积冰加重;气温和风速在两次积冰过程的形成阶段起到主要作用。
Both direct and indirect effects of freezing drizzle on ice accretion were analyzed for ten freezing drizzle events during a comprehensive ice thickness, fog, and precipitation observation campaign carried out during the winter of 2008 and 2009 at Enshi Radar Station (30°17′N, 109°16′E), Hubei Province, China. The growth rate of ice thickness was 0.85 mm h-1 during the freezing drizzle period, while the rate was only 0:4 mm h-1 without sleet and freezing drizzle. The rain intensity, liquid water content (LWC), and diameter of freezing drizzle stayed at low values. The development of microphysical properties of fog was suppressed in the freezing drizzle period. A threshold diameter (Dc) was proposed to estimate the influence of freezing drizzle on different size ranges of fog droplets. Fog droplets with a diameter less than Dc would be affected slightly by freezing drizzle, while larger fog droplets would be affected significantly. Dc had a correlation with the average rain intensity, with a correlation coefficient of 0.78. The relationships among the microphysical properties of fog droplets were all positive when the effect of freezing drizzle was weak, while they became poor positive correlations, or even negative correlations during freezing drizzle period. The direct contribution of freezing drizzle to ice thickness was about 14.5%. Considering both the direct and indirect effects, we suggest that freezing drizzle could act as a "catalyst" causing serious icing conditions.
The weather system, meteorological conditions, and microphysics of cloud, fog, and rain droplets are studied during the formation, growth, maintenance, and shedding periods of ice accretion on wires in Enshi, Hubei Province in China using 2008/2009 and 2009/2010 winter observations. The comprehensive observations include data of visibility, microphysics of fog and rain droplets, and ice thickness, as well as data from an automated weather station and other routinely recorded meteorological data. The results show that icing occurred during the passage of a cold front, with a high-pressure system and a cold temperature trough at 850 hPa, and a southeasterly at 500 hPa that provided abundant moisture. Ice formation usually started in the evening or early morning, and ice shed around noon the following day when the temperature was -1℃ to 0℃. The averaged liquid water content of the fog droplet was distinctly greater during the growth period than during the other three periods, and there was precipitation during the growth period in each case of ice accretion. The growth rate of the ice thickness was clearly correlated with the liquid water content, with a correlation coefficient of 0.62. Simulations using empirical equations were carried out, and the simulated ice thickness agreed with observations fairly well.
Data collected in the surface layer in a northern suburban area of Nanjing from 15 November to 29 December 2007 were analyzed to examine the MoninObukhov similarity for describing the turbulent fluctu ations of 3D winds under all stability conditions and to obtain the turbulence characteristics under different weather conditions. The results show that the dimensionless standard deviations of turbulent velocity com ponents (σ u /u* , σ v /u* , σ w /u * ) and dimensionless turbulent kinetic energy (TKE) can be well described by "1/3" power law relationships under stable, neutral, and unstable conditions, with σ u /u * σ v /u * σ w /u* . Land use and land cover changes mainly impact dimensionless standard deviations of horizontal component fluctuations, but they have very little on those of the vertical component. The dimensionless standard devi ations of wind components and dimensionless TKE are remarkably affected by different weather conditions; the deviations of horizontal wind component and dimensionless TKE present fog day clear sky overcast cloudy; the trend of the vertical wind component is the reverse. The surface drag coefficient at a Nan jing suburban measurement site during the observation period was obviously higher than at other reported plains and plateau areas, and was approximately one order larger in magnitude than the reported plains areas. Dimensionless standard deviation of temperature declined with increasing |z /L| with an approximate "1/3" slope in unstable stratification and "2/3" slope in stable stratification.